https://www.tnp-instruuments.com/021a5a61a75c4103ae965951895bb658
Secure Checkout
IPAQ C330 Universal Programmable 2-wire 4 to 20mA Temperature Transmitter

Thumbnail Filmstrip of IPAQ C330 Universal Programmable 2-wire 4 to 20mA Temperature Transmitter Images

    IPAQ C330 Universal Programmable 2-wire 4 to 20mA Temperature Transmitter

    Overview

    IPAQ C330 is a modern temperature transmitter developed to meet the highest requirements on flexibility, accuracy and reliability. A universal transmitter compatible with RTD, thermocouples, voltage and potentiometer sensors to offer high flexibility and reduce the number of installed product variants. IPAQ C330 is available with ATEX, IECEx and cFMus certifications, making it a safe choice for a wide range of applications. The IPAQ C330 is scalable over the entire range of 7 types of RTDs and 10 Thermocouple Types; as well as accepting Millivolt and Resistance inputs.
    Features
    • High accuracy and long term stability
    • Universal Input - Accepts RTD, T/C, mV and Ω
    • 50-point Customized Linearization and Callendar-Van Dusen/li>
    • Sensor error and system (sensor/transmitter) error correction for highest total accuracy
    • Low temperature drift
    • Configuration via USB or NFC without external power
    • Rugged design tested for 10 g vibrations
    • High security - Password protection and date of changes logged
    Price Starting At:
    $208.00
    Need help? Contact us with questions.

      Shipping Estimated 1 week.
    Click Add to Cart to Select Temperature Sensor, Scale and Range
    Please add 1 Week to Estimated Shipping for Configuration
    IPAQ C330 Programmable Transmitter Specifications
    Input Types Thermocouple - J, K, T, E, N, R, S, B, C, D
    RTD - Pt100 (IEC 60751, α = 0.00385) AND (JIS C1604-1981, α = 0.003916),
    Ni100, Ni120, Ni1000, Cu10, resistance / potentiometer
    Sensor Range, Accuracy, Minimum Span See Range and Accuracy Table Below
    Output 4-20 mA / 20-4 mA, temperature linear
    Operating temperature -40 to +185 °F (-40 to +85°C)
    Galvanic isolation 1500 VAC, 1 min
    Power Supply IPAQ C330 8.0 to 36.0 VDC
    IPAQ C330X 8.0 to 30.0 VDC
    Measuring Accuracy Accuracy & stability - Basic accuracy is max. of ±0.08°C or ±0.08% of span
    Ambient Temperature Influence Thermocouple and RTD: See Table Below
    Resistance - ±0.01% < 4000 Ω (2000 Ω at 2-wire) < ±0.02% of span per °C
    Voltage: ±0.01% of span per °C
    Supply Voltage Influence <±0.005% of span per V
    Long Term Drift Max. of ±0.02°C or ±0.02% of span per year
    Operating and Storage Temperature Standard version: -40 to +185°F (-40 to +85°C)
    Intrinsically safe transmitters
    Temperature Class T6 - Ambient temperature Ta -40°C ≤ Ta ≤ +60°C / -40°F ≤ Ta ≤ +140°F
    Temperature Class T5 - Ambient temperature Ta -40°C ≤ Ta ≤ +75°C / -40°F ≤ Ta ≤ +167°F
    Temperature Class T4 - Ambient temperature Ta -40°C ≤ Ta ≤ +85°C / -40°F ≤ Ta ≤ +185°F
    Humidity 0 to 98% RH (non-condensing)
    Protection Category Housing: IP65
    Terminals: IP00
    Housing Materials Jouding PC/ABS + PA
    Flammability according to UL VO
    Thermocouple Range, Accuracy and Minimum Span Table
    <
    Sensor Type Temperature Range °F/°C Minimum Span °F/°C Accuracy (maximum of) °F/°C Temp. influence (Dev. from ref. temp. 20°C) °F/°C
    Type K (NiCr-NiAl) -454 to +2372°F
    -270.to.+1300°C
    90°F
    50°C
    ±0.9°F or ±0.1% of span (2)*
    ±0.5°C or ±0.1% of span (2)*
    ±0.006% of span per °F
    ±0.01% of span per °C
    Type J (Fe-CuNi) -346 to +2192°F
    -210.to.+1200°C
    90°F
    50°C
    ±0.9°F or ±0.1% of span (2)*
    ±0.5°C or ±0.1% of span (2)*
    ±0.006% of span per °F
    ±0.01% of span per °C
    Type T (Cu-CuNi) -454 to +752°F
    -270.to.+400°C
    90°F
    50°C
    ±0.9°F or ±0.1% of span (2)*
    ±0.25°C or ±0.2% of span (2)*
    ±0.006% of span per °F
    ±0.01% of span per °C
    Type E (NiCr-CuNi) -454 to +1832 °F
    -270.to.+1000 °C
    90°F
    50°C
    ±0.9°F or ±0.1% of span 2 °F (2)*
    ±0.5°C or ±0.1% of span °C (2)*
    ±0.01% of span per °C
    Type N (NiCrSi-NiSiMg) 148 to +2372°F
    -100.to.+1300°C
    180°F
    100°C
    ±0.9°F or ±0.1% of span (2)*
    ±0.5°C or ±0.1% of span (2)*
    ±0.006% of span per F°
    ±0.01% of span per °C
    Type N (NiCrSi-NiSiMg) -454 to -148 F°
    -270.to.-100°C
    180°F
    100°C
    ±1.8°F (2)*
    ±1.0 °C(2)*
    ±0.18% of span per °F
    ±1.0°C or ±0.1% of span (2)*
    S (Pt10%Rh-Pt) -58 to +3182F°
    -50.to.+1750°C
    540°F
    300°C
    ±1.8°F or ±0.1% of span 2
    ±1.0°C or ±0.1% of span (2)*
    ±0.006% of span per °F
    ±0.1% of span per °C
    R (Pt13%Rh-Pt) -58 to +3182F°
    -50.to.+1750°C
    540°F
    300°C
    ±1.8°F or ±0.1% of span 2
    ±1.0°C or ±0.1% of span (2)*
    ±0.006% of span per °F
    ±0.1% of span per °C
    B (Pt30%Rh-Pt6%Rh) +752 to +3272F°
    +400.to.+1800C°
    1260F°
    700°C
    ±1.8°F or ±0.1% of span (2)*
    ±1.0°C or ±0.1% of span (2)*
    ±0.006% of span per °F
    ±0.1% of span per °C
    C (W5%Re-W26%Re) +32 to +4199°F (2)*
    0.to.+2315°C
    360F°
    200°C
    ±1.8°F or ±0.1% of span (2)*
    ±1.0°C or ±0.2% of span (2)*
    ±0.006% of span per °F
    ±0.1% of span per °C
    D (W3%Re-W25%Re) +32 to +4199°F (2)*
    0.to.+2315°C
    360F°
    200°C
    ±1.8°F or ±0.1% of span (2)*
    ±1.0°C or ±0.2% of span (2)*
    ±0.006% of span per °F
    ±0.1% of span per °C
    *Note 2 CJC error not included. ≤ 0.9°F within ambient temperature range
    *Note 2 CJC error not included. ≤ 0.5°C within ambient temperature range
    RTD Range, Accuracy and Minimum Span Table
    Sensor Type Temperature Range °F/°C Minimum Span °F/°C Accuracy (maximum of) °F/°C Temp. influence (Dev. from ref. temp. 68°F/20°C) °F/°C
    RTD Pt100 (α =0.00385) (1)* -328 to +1562°F
    -200 to +850°C
    18°F
    10°C
    ±0.18°F or ±0.1% of span
    ±0.08°C or ±0.08% of span
    ±0.006% of span per °F
    ±0.1% of span per °C
    RTD Pt100 (α=0.003916) (2)* -328 to +1562°F
    -200 to +850°C
    18°F
    10°C
    ±0.18°F or ±0.1% of span
    ±0.08°C or ±0.08% of span
    ±0.006% of span per °F
    ±0.1% of span per °C
    RTD PtX (1)* Corresp. to max.4 k 18°F
    10°C
    ±0.18°F or ±0.1% of span
    ±.1°C or ±0.1% of span
    ±0.006% of span per°F
    ±0.01% of span per °C
    RTD Ni100 (3)* -76 to +482°F
    -60.to.+250°C
    18°F
    10°C
    ±0.18°F or ±0.1% of span
    ±0.1°C or ±0.1% of span
    ±0.006% of span per °F
    ±0.01% of span per °C
    RTD Ni120 (4)* -76 to +482°F
    -60.to.+250°C
    18°F
    10°C
    ±0.18°F or ±0.1% of span
    ±0.1°C or ±0.1% of span
    ±0.006% of span per °F
    ±0.01% of span per °C
    RTD Ni1000 (3)* -58 to +356°F
    -50.to.+180
    18°F
    10°C
    ±0.18°F or ±0.1% of span
    ±0.1°C or ±0.1% of span
    ±0.006% of span per °F
    ±0.01% of span per °C
    RTD Cu10 (Edison Copper Windings No. 15) -58 to +392°F
    -50.to.+250°C
    149°F
    83°C
    ±2.7°F or ±0.2% of span
    ±1.5°C or ±0.2% of span
    ±0.006% of span per °F
    ±0.02% of span per °C
    TECHNICAL DATA
    Sensor Current Sensor current ≤300 μA
    Maximum sensor wire resistance 3-wire and 4-wire connection
    50 Ω/wire
    2-wire connection
    Compensation for 0 to 100 Ω loop resistance
    Adjustment Minimum span 10°C / 18°F
    Sensor error compensation ±10% of span for span <50°C / 90°F, otherwise ±5°C/±9°F
    Intrinsic Safety Approvals
    PART NUMBER DESCRIPTION IS RATINGS
    70C330X012 IPAQ C330X (ATEX, IECEx) II 1 G Ex ia IIC T6…T4 Ga
    70C330F012
    IPAQ C330X (cFMus, ATEX, IECEx) Ex ia IIC T6…T4 Ga
    70C330F012
    IPAQ C330X (cFMus, ATEX, IECEx)
    IPAQ C330X FM CA
    IS CL I Div 1 GP A-D, T6…T46)
    Cl I Zn 0 AEx/Ex ia IIC T6…T4 Ga6)
    *Notes: 1) IEC 60751, 2) JIS C 1604, 3) DIN 43760, 4) Edison No. 7, 5) Edison No. 15, 6) T6...T4 are depending on effect Notes 2* CJC error not included. ≤ 0.9°F within ambient temperature range
    CJC error not included. ≤ 0.5°C within ambient temperature range