Log In        Register

HXG-3 UL 913 Intrinsic Safety Combustible Gas Leak Detector

Warning: To reduce the risk of ignition of a flammable atmosphere, batteries must only be changed in an area known to be nonflammable.
Warning and Precaution
The Combustible GAS detector is a leak locating tool and is not intended for use as a confined-space, personal safety tool. It will not specifically identify a gas or a CFC, and it does not tell you the precise level of a combustible gas or CFC that may be present. High concentrations of combustible gas/CFC can cause explosions, fires, asphyxia, and other hazards that could cause serious personal injury or death. Be informed on the characteristics and hazards of the gas/CFC you are working with, and use proper precautions to avoid hazardous atmospheres.
HXG-3 UL 913 Intrinsic Safe Combustible Gas Leak Detector
    Price Starting At: $710.00

    Overview

    Features
    • Gases Detected (partial listing): Methane, Natural Gas, Ammonia, Hydrogen, Butane, Propane, Acetone, Gasoline, Halon, Jet Fuel, Refrigerants, Ethylene Oxide, Lacquer Thinner, Industrial Solvents
    • UL 913 intrinsic safety rating*
    • Combustible Gas Leak Detector capable of displaying ppm or %LEL (Lower Explosive Limit)
    • 10ppm (methane) Sensitivity
    • Instant response
    • Electronic tick rate control
    • Audio and Visual alarm indication with settable alarm
    • 16" Length Flexible Goose Neck Probe
    * SENSIT® HXG-3 instruments are approved UL913, For Class 1, Division 1, Groups C, D, T3 hazardous locations when used with Duracell MN1400BK batteries or equivalent alkaline batteries.
    Applications
    • Utility Companies
    • Gas Processing Plants
    • Safety Engineers
    • Fire and Police
    • Emergency Vehicles
    • Plant Maintenance
    • Plumbing Contractors
    • Furnace Heat Exchanger Testing
    • Heating and Air Conditioning
    • Municipalities
      Shipping Estimated Shipping 1 to 3 Weeks

    HXG-3 Combustible Gas Leak Detector Specifications
    Combustible Gasses Detected (Partial List) Methane, Natural Gas, Ammonia, Hydrogen, Butane, Propane, Acetone, Gasoline, Halon, Jet Fuel, Refrigerants, Ethylene Oxide, Lacquer Thinner, Industrial Solvents
    Sensor Sensitivity 10ppm (methane)
    Sensor Type Low power semiconductor
    Display type Two line digital with backlight
    Probe Length 16"
    Leak Indication Audio/Visual
    Adjustable Tic Rate Yes
    Alarms Audible/Visual (User settable)
    Leak level read out Yes, 0 to 50,000ppm
    %LEL Indication Yes, 0% to 100%
    Internal Sample Pump No
    Intrinsic Safety Rated Yes, UL 913*
    Battery Type 3 "C" alkaline batteries
    Battery Life approximately 25 hrs. continuous
    Size 11.5" x 3" x 2.32" (292 x 76 x 69 mm)
    Weight 1.3 lb
    * SENSIT® HXG-3 instruments are approved UL913, For Class 1, Division 1, Groups C, D, T3 hazardous locations when used with Duracell MN1400BK batteries or equivalent alkaline batteries.
    HXG-3 UL 913 Intrinsic Safety Rating Combustible Gas Leak Detector includes Hard Carrying Case, 3 “C” Batteries, Wrist Strap and Instruction Manual Warning: To reduce the risk of ignition of a flammable atmosphere, batteries must only be changed in an area known to be nonflammable.
    Warning and Precaution
    The Combustible GAS detector is a leak locating tool and is not intended for use as a confined-space, personal safety tool. It will not specifically identify a gas or a CFC, and it does not tell you the precise level of a combustible gas or CFC that may be present. High concentrations of combustible gas/CFC can cause explosions, fires, asphyxia, and other hazards that could cause serious personal injury or death. Be informed on the characteristics and hazards of the gas/CFC you are working with, and use proper precautions to avoid hazardous atmospheres.